PRO-series DC charger Maintenance Manual

Modified on Tue, 20 Oct at 8:51 PM

TABLE OF CONTENTS




PART 1 Fault & Alarm Code


When there is a fault code on the display and an alarm code on the backend, please contact your local installer for assistance to solve the problem or contact Morek EV support through Morek EV Wiki.


Please note that the disappearance of the alarm does not mean that the problem has been resolved. Please contact us promptly, and we will provide a solution to the problem


Fauld Code
Alarm type
Alarm code
Alarm disappearing conditions
49Main output contactor failure35The alarm disappears after powering off
52Fuse failure59The alarm disappears after powering off
53Lightning protection failure78The alarm disappears after powering off
60Vehicle port voltage is negative61The alarm can be cleared after pulling out the charging cable.
61AC input overvoltage82The following conditions must be met at the same time for 10 seconds, the alarm disappears:
1. In the host state, there are modules online, the AC contactor is closed, and the system emergency stop
button is not triggered;
2. The AC side of the module is powered on and the module is online;
3. The minimum value of the 3-phase voltage of the module <180V & and the maximum value of the 3-
phase voltage of the module is >243V. The number of modules that meet this condition > 0.
 for 60kW systems, the alarm disappears when the system is powered off;
62AC input undervoltage81The following conditions must be met at the same time for 10 seconds, the alarm disappears:
1. In the host state, there are modules online, the AC contactor is closed, and the system emergency stop
button is not triggered;
2. The AC side of the module is powered on and the module is online;
3. The minimum value of the 3-phase voltage of the module <180V & and the maximum value of the 3-
phase voltage of the module is >243V. The number of modules that meet this condition > 0.
 for 60kW systems, the alarm disappears when the system is powered off;
66AC input phase A is missing.83The following conditions must be met at the same time for 10 seconds, the alarm disappears:
1. In the host state, there are modules online, the AC contactor is closed, and the system emergency stop
button is not triggered;
2. The AC side of the module is powered on and the module is online;
3. The minimum value of the 3-phase voltage of the module <180V & and the maximum value of the 3-
phase voltage of the module is >243V. The number of modules that meet this condition > 0.
 for 60kW systems, the alarm disappears when the system is powered off;
67AC input phase B is missing.83The following conditions must be met at the same time for 10 seconds, the alarm disappears:
1. In the host state, there are modules online, the AC contactor is closed, and the system emergency stop
button is not triggered;
2. The AC side of the module is powered on and the module is online;
3. The minimum value of the 3-phase voltage of the module <180V & and the maximum value of the 3-
phase voltage of the module is >243V. The number of modules that meet this condition > 0.
 for 60kW systems, the alarm disappears when the system is powered off;
68AC input phase C is missing.83The following conditions must be met at the same time for 10 seconds, the alarm disappears:
1. In the host state, there are modules online, the AC contactor is closed, and the system emergency stop
button is not triggered;
2. The AC side of the module is powered on and the module is online;
3. The minimum value of the 3-phase voltage of the module <180V & and the maximum value of the 3-
phase voltage of the module is >243V. The number of modules that meet this condition > 0.
 for 60kW systems, the alarm disappears when the system is powered off;
76The system has no available
 modules
84
80Meter offline36When the meter communication is normal, the alarm disappears.
83insulation failure39The alarm can be cleared after disconnecting the charging cable from the charger.
84System module mixed insertion87The alarm disappears after powering off the charger.
85System emergency stop failure73After reset the emergency stop button, the alarm disappears.
86Master-slave communication
 abnormality
76When Master-slave communication is restored, the alarm disappears
87Meter calibration error42Pull out the charging cable and the alarm disappears; or power off the charger and the alarm disappears.
88System door sensor failure77When the door is closed, the alarm disappears.
89System fan failure79The alarm disappears after powering off the charger.
95Duplicate TMU ID40The alarm disappears after powering off the charger.
135Charging system does not
 match
65The alarm disappears after powering off the charger.
136Module startup failed69The alarm disappears after the charging cable is disconnected from the vehicle.
177Gun tip over temperature
 warning
1078
1. In standard mode, if the temperature of the charging cable connector<60℃ (when the charging session is
finished or when the charger is at idle state) and lasts for 10 seconds, the alarm disappears;
2. In standard mode, the alarm disappears after disconnecting the charging cable from vehile for 10
 seconds.
186Duplicate CMU ID88The alarm disappears after powering off the charger.
257IO board offline257
the alarm disappears after the communication between PCU and CMU is normal.
258IO board failure258
1. For IO board fault alarms triggered by IOB address anomalies and IOB command overruns, the alarms
disappear after powering off;
2. For IO board fault alarms triggered by IO board offline and IO board interlocking, refer to the respective
 alarm disappearance conditions.
259TMU interlock abnormality1065
The alarm disappears after the charging cable is disconnected from the vehicle.
260Abnormal voltage in front of
 output contactor
1066The alarm disappears after the charging cable is disconnected from the vehicle.
261The module address is out of
 range or the address is repeated
1341The alarm disappears after powering off the charger.
262Module slot mismatch1342The alarm disappears after powering off the charger.
263TMU emergency stop failure1069The alarm disappears after emergency stop button of the terminal is reset.
265TMU door sensor failure1070The alarm disappears when the terminal cabinet door is closed.
266IO interlock fault259
There is no such failure for single charging station.
267CMU interlock failure1344
For the 120kw system, the alarm disappears as long as one of the following conditions is met,
1. All charging cables of online terminals have been disconnected from vehicles;
2. The terminals are all in not charging state && the number of terminals with their charging cables
disconnected from vehicle are not 0.
3. There is only one terminal at charging state at most;
 4. All parallel contactors are open.
268CMU has no available module
 failure
1345
If the charger system has available modules, the fault disappears.
269AC input contactor refuses to
 operate/ malfunctions
1346
The alarm disappears after powering off the charger.
270AC input adhesion failure1347
The alarm disappears after powering off the charger.
272Bleed circuit failure1071
When the output voltage drops below 60V, the fault disappears.
273TMU no module available fault1068
For 180KW, if the terminal system has available modules, the fault disappears;
275TCU offline fault1099
1. The communication between the monitor and the TCU is normal, and the alarm disappears; 2. Under the
non-TCU mode, the communication between the monitor and the master central control is normal, and the
 alarm disappears;
276Meter shunt counterattack1100
The alarm disappears after powering off the charger.






PART 2 Routine Check and Maintenance


1. Routine check: periodic checks are mainly carried out to ensure the normal operation of equipment. The check content mainly involves on-site charging stations, fire protection, environment, safety, etc. If non-equipment problems occur, please report to the owner for corresponding actions.

Please fill in the “Equipment Maintenance Record” to track the operation of the charging station.


2. Maintenance: Maintain the discovered problems and hidden dangers.



 Equipment Maintenance Record

No.TypeNo.ContentCheck MethodRecommended
 Frequency
RequirementsResults
1Solve problem
 of Fault/Alarm
1
Firmware upgrade/
replace spare parts/
 confirmation
when there is a
 fault/alarm
1. Please confirm spare
parts specification
before and after
replacement;
2. please confirm
firmware version
before and after
 replacement.
SolvedPending
2
when there is a
 fault/alarm
SolvedPending
3
when there is a
 fault/alarm
SolvedPending
2charging cable
 check
41. Check whether the charging cable is in tact
and whether replacement is required.
2. If the charging cable is damaged, please
replace the charging cable.
3. After replacement is completed, please
check the phase sequence of DC±, A±, S±,
CC1 and PE, and please check whether the
 wiring of the charging cable is tight.
visual check
 wiring check
every 3 months1. after replacement is
completed, please
calibrate the charging
 cable.
SolvedPending
3dust filter
 check
5Check the air inlet and outlet dust filters of the
cabinet for blockage and clean them if
necessary.
The dust filter is a wearing part and needs to
 be replaced if it is damaged.
visual checkevery month1. Clean and dry the
dust filter before
 reinstalling it.
SolvedPending
4Site safety
 check
6Are there any cracks in the exposed
 construction wiring?
visual checkevery 3 months
PassFail
7Is the on-site firefighting equipment fully
 equipped?
visual checkevery 3 monthsPassFail
8Are the vehicle barriers and anti-collision
 pillars in front of the charging station secure?
visual checkevery 3 monthsPassFail
9Is there serious water accumulation around the
 equipment?
visual checkevery 3 monthsPassFail
10If the charging station reports over
temperature and the filter has serious dust
accumulation, the dust filter needs to be
 cleaned/ replaced immediately.
visual checkevery monthPassFail
5

Function check

11check whether the display screen is normal,
the touch control is normal, and there is no
 screen blur or screen flickering.
visual checkevery 3 months
PassFail
12the mechanical lock on the charging cable
 connector is locked and released normally.
visual check/testevery 3 months
PassFail
13The power module works in normal state, the
output is normal, there are no abnormal
alarms, and the module fan makes no
 abnormal noise.
visual
check/backend
 check
every 3 months
PassFail
14The charging stations are online, network
communication is normal, QR code scan is
 normal.
display
 check/visual check
every 3 months
PassFail
15The lightning protector is normal, there is no
 breakdown, and the system has no alarms.
visual checkevery 3 months
PassFail
16Anti-tipping, anti-water immersion device,
 and access control without error triggering
backend checkevery 3 months
PassFail
6Cabinet check17there is no dust or painting on the charging
 station. there is no damage to the antenna.
visual checkevery 3 months
PassFail
18the charging station is installed vertically on
 the ground, not loose or tilted
visual checkevery 3 months
PassFail
19the charging station cabinet, housing and door
have no deforamtion, impact, damaged, paint
 peeling, rusts, scratches.
visual checkevery 3 months
PassFail
20The QR codes or related logos, nameplates,
etc. affixed to the charging stations are not
 faded or peeled off.
visual checkevery 3 months
PassFail
21The charging cable is placed at its normal
position, with no damage or serious wearness;
the cable connectors are not loose or
 deformed.
visual checkevery 3 months
PassFail
7Inside Cabinet
 check
22The internal and external ground connections
of the charging stations are reliable, without
 breakage, blackening, corrosion or damage.
visual checkevery 3 months
PassFail
23There are no abnormal sounds (such as
buzzing) from the relays in the charging
stations, and there is no peculiar smell or
 burning smell.
visual check/smellevery 3 months
PassFail
24There is no leakage, water stains, water
accumulation, or rusty screws inside the
 charging station.
visual checkevery 3 months
PassFail
25The cable inlet at the bottom of the charging
station is tightly sealed with fireproof mud and
 has no cracks.
visual checkevery 3 months
PassFail
26The terminals and wiring of the main control
board of the charging station are not loose and
inserted in place; the components are not
 damaged.
visual checkevery 3 months
PassFail