Charging cable (DC) installation

Modified on Fri, 24 Jan at 10:25 AM

DC power cable connections:

◦    Black to negative (-)

◦    Red to positive (+)

◦    Yellow/Green to Protective Earth (PE)


Communication wire connections:

◦    Blue (BU) and Orange (OG) in terminals 1 and 2

◦    White (WH) and Violet (VT) in terminals 3 and 4

◦    Control Pilot (CP) to terminal 5


* Proximity Pilot (PP) is not used


Cable ends must be prepared with appropriate cable terminal ends. The M8 bolts securing DC+, DC- and PE terminals to the busbars must be tightened up to 13 Nm of torque. For the smaller cables, simple ferrules can be used. 


ModelCable amountCross-section
30 kW13 x 16 mm² + 3 x 2 x 0.75 mm²
60 kW22 x 35 mm² + 1 x 25 mm² + 3 x 2 x 0.75 mm²
120 kW22 x 50 mm² + 1 x 25 mm² + 3 x 2 x 0.75 mm²
180 kW22 x 70 mm² + 1 x 35 mm² + 3 x 2 x 0.75 mm²


180/120/60 kW:


30 kW: