DC power cable connections:
◦ Black to negative (-)
◦ Red to positive (+)
◦ Yellow/Green to Protective Earth (PE)
Communication wire connections:
◦ Blue (BU) and Orange (OG) in terminals 1 and 2
◦ White (WH) and Violet (VT) in terminals 3 and 4
◦ Control Pilot (CP) to terminal 5
* Proximity Pilot (PP) is not used
Cable ends must be prepared with appropriate cable terminal ends. The M8 bolts securing DC+, DC- and PE terminals to the busbars must be tightened up to 13 Nm of torque. For the smaller cables, simple ferrules can be used.
Model | Cable amount | Cross-section |
30 kW | 1 | 3 x 16 mm² + 3 x 2 x 0.75 mm² |
60 kW | 2 | 2 x 35 mm² + 1 x 25 mm² + 3 x 2 x 0.75 mm² |
120 kW | 2 | 2 x 50 mm² + 1 x 25 mm² + 3 x 2 x 0.75 mm² |
180 kW | 2 | 2 x 70 mm² + 1 x 35 mm² + 3 x 2 x 0.75 mm² |
180/120/60 kW:
30 kW: